Chilled Beam: Cooling With Water Instead of Air
A chilled beam is a ceiling unit that cools a room by passing chilled water through a coil, with no fan of its own. Passive beams cool by natural convection; active beams use the building's fresh air supply to draw room air across the coil. Because the coil runs above the room's dew point, the beam handles sensible heat only, so humidity must be controlled separately.
By Dhruv Agarwal · · 2 min read
Why it matters on a project
Chilled beams are quiet, efficient and low-maintenance, which makes them attractive in premium offices. They are also unforgiving: a system that is well suited to a dry climate can drip on desks in a humid one if the moisture side of the design is treated as an afterthought.
Active versus passive
| Passive beam | Active beam | |
|---|---|---|
| Air connection | None | Primary fresh air through nozzles |
| How room air moves | Natural convection | Induced by the primary air jets |
| Cooling capacity | Lower | Higher per metre |
| Provides ventilation | No, needs a separate system | Yes |
| Testing and rating | EN 14518 | EN 15116 |
The one rule: stay above the dew point
The coil must run warmer than the dew point of the room air. That means:
- Fresh air dehumidified centrally, usually by a dedicated outdoor air unit, so it carries the room's moisture load.
- Chilled water supplied warmer than for fan coil units, with controls that track room dew point.
- Condensation sensors on the pipework or beam, interlocked to close valves or raise water temperature.
- An airtight building, because humid outside air leaking in brings moisture the beams cannot remove.
Ventilation rates are set under ASHRAE 62.1, within the air conditioning provisions of NBC 2016, Part 8.
Common mistakes
- Treating beams as a straight swap for fan coils without redesigning the fresh air plant.
- Leaving windows or doors open in a beam-cooled space during the humid season.
- No dew point controls, or sensors installed but not commissioned.
- Too little ceiling void for beams, water pipework and the primary air ductwork together.
- Layouts that change often, where every move involves water connections.
Standards referenced
Active beams are tested and rated under EN 15116, passive beams under EN 14518; ventilation under ASHRAE 62.1; air conditioning provisions in NBC 2016, Part 8. Whether chilled beams suit a specific building, and their water temperatures and controls, must be established by the project's HVAC consultant.
Standards referenced
- EN 15116 — Ventilation in buildings — chilled beams — testing and rating of active chilled beams (CEN-CENELEC)
- EN 14518 — Ventilation for buildings — chilled beams — testing and rating of passive chilled beams (CEN-CENELEC)
- ASHRAE 62.1 — Ventilation for acceptable indoor air quality (ASHRAE)
- NBC 2016, Part 8 — Building services — air conditioning (Bureau of Indian Standards)
Frequently asked
Related
- Fan Coil Unit: The Workhorse of Chilled Water Cooling
- Condensate Drainage: The Small Pipe Behind Most Ceiling Stains
- Air Handling Unit: What an AHU Does and What It Needs
- VAV System: Variable Air Volume Cooling
- VRF vs Chiller for an Office: Load, Floor Plate and Running Cost
- Interstitial Condensation: Moisture Inside the Wall or Roof