Fire Dampers — Types, Ratings and Installation
By Dhruv Agarwal · · 1 min read
What it is
A closure device inside ductwork at the point it crosses a fire compartment boundary, restoring the fire resistance of the wall or floor it passes through.
Types
| Type | Actuation | Typical use |
|---|---|---|
| Fire damper | Fusible link, heat | General compartment crossings |
| Fire-smoke damper | Motorised, alarm signal | Escape routes, pressurisation |
| Smoke damper | Motorised, detection | Smoke control systems |
| Ceiling radiation damper | Heat | Ceiling penetrations in rated floors |
Specification at a glance
| Property | Typical specification |
|---|---|
| Rating | Matches the wall or floor rating — 60, 120 minutes |
| Standard | EN 15650 or UL 555 |
| Link temperature | Commonly 72°C for fire dampers |
| Frame | Purpose-made installation frame, built into the wall |
| Actuator | Spring-return on motorised types |
| Access | Panel sized and positioned to reach the damper |
Installation is where the rating lives
A correctly rated damper installed badly gives no protection at all:
- The damper must be built into the wall on its installation frame, not hung off the duct beside it
- The gap around the frame must be fire-stopped with a tested system
- The duct must be able to fall away in a fire without pulling the damper out
- An access panel must reach the damper for testing and resetting
- Links and blades must be clear of paint and free to move
Where projects go wrong
- No access panel. The damper can never be tested or reset.
- Fixed to the duct, not the wall.
- Fire stopping done with general-purpose sealant rather than a tested system.
- Rating lower than the wall it penetrates.
- Fire-smoke damper specified but wired to nothing, so it never closes on alarm.
Standards referenced
Compartmentation and services provisions under NBC 2016, Part 4. Fire damper requirements under EN 15650 and UL 555.
Standards referenced
- NBC 2016, Part 4 — Fire and life safety — compartmentation and services
- EN 15650 — Ventilation for buildings — fire dampers
- UL 555 — Standard for fire dampers