Pre-Insulated Duct — PIR Panel Ductwork

By Dhruv Agarwal · · 1 min read

What it is

Ductwork made from rigid PIR panel faced with aluminium on both sides, cut and folded into sections on site. The insulation and the duct are the same component.

Specification at a glance

PropertyTypical specification
PanelPIR core, aluminium facings both sides
Panel thickness20mm — 30mm typical
FacingAluminium foil, thickness stated
StandardEN 13403 for non-metallic ducts
Fire classNamed EN 13501-1 classification
Pressure limitStated by manufacturer; not unlimited

Against GI ductwork

Pre-insulated PIRGI with wrap
Void height neededLessMore
WeightMuch lighterHeavy
Install sequenceOne operationFabricate, fit, then insulate
RobustnessLower; damages easilyHigh
Pressure capabilityLimitedWide range
Outdoor useNeeds weather jacketStandard

Where it earns its place

Tight ceiling voids in fit-outs where the slab-to-slab height is fixed and services must be stacked · refurbishments where structural hanger capacity is limited · fast-track programmes where removing the separate insulation trade saves real days · low and medium pressure comfort cooling in office space.

Where projects go wrong

  • Used in the wrong location — kitchen extract, exposed plant rooms, or outdoors without a jacket.
  • Fire class not checked against the route the duct takes.
  • Joints poorly made. The system relies on correct corner profiles and taping; a rushed joint leaks and the aluminium facing tears.
  • Hangers over-tightened, crushing the panel and reducing the free area.
  • Pressure class exceeded, causing panel deflection and joint failure.

Standards referenced

Non-metallic duct requirements under EN 13403. Reaction-to-fire classification to EN 13501-1. Duct insulation requirements under ECBC 2017.

Standards referenced

  • EN 13403Ventilation for buildings — non-metallic ducts
  • EN 13501-1Reaction to fire classification
  • ECBC 2017HVAC — duct insulation