Office CO2 and Fresh Air: How ASHRAE 62.1 Sets Ventilation

An office's fresh air requirement is the outdoor air supplied to dilute what people and the building release. ASHRAE 62.1's ventilation rate procedure sets it from two parts, a rate per person and a rate per unit floor area, applied to the real occupancy. CO2 shows whether that air is reaching people; it is an indicator, not a pollutant limit, and air changes per hour do not measure it.

By Dhruv Agarwal · · 7 min read

Drowsy afternoons are usually a ventilation problem

Ask people on a crowded office floor how they feel at four in the afternoon and a familiar set of complaints comes back: heavy heads, stale air, meeting rooms nobody wants to sit in for long. The usual response is to turn the thermostat down. The room gets colder and nothing improves.

That is because the complaint is rarely about temperature. Cooling removes heat; ventilation replaces the air people have breathed. Most office air conditioning recirculates the same air through the cooling coil and back into the room. The outdoor air that dilutes what occupants exhale is a separate, deliberately sized quantity, and it is the one most often undersized, poorly distributed or turned down to save energy.

For a business, the cost is not the air conditioning bill. It is a floor that people tolerate rather than use, meeting rooms avoided after lunch, and a facilities team chasing a temperature complaint that is really a ventilation one.

How ASHRAE 62.1 sets outdoor air for an office

ASHRAE 62.1, Ventilation and Acceptable Indoor Air Quality, is the standard most commonly referenced for office ventilation design in India, alongside the air conditioning and ventilation provisions of NBC 2016, Part 8. Its ventilation rate procedure builds the outdoor air requirement for a zone from two parts:

  • A people component: a rate per person multiplied by the number of people the zone is designed for. It covers what occupants themselves release, such as exhaled breath and body odour.
  • An area component: a rate per unit floor area multiplied by the zone's area. It covers what the building releases regardless of headcount, such as emissions from finishes, furniture and equipment.

The sum is then adjusted for how effectively the air distribution actually delivers outdoor air to the breathing zone, and, where one system serves several zones, for how efficiently it shares that air between them. The rates for each type of space are tabulated in the standard and revised between editions, so the design engineer sets the values from the edition adopted in the project's design basis. This page explains the method; it does not give the numbers.

The commercial consequence sits in the people component. Because it scales with headcount, densifying a floor raises the requirement. A system sized for one seating density will under-ventilate the same floor after it has been re-planned with more desks, and a small meeting room that seats many people for an hour needs far more outdoor air per square metre than the open plan beside it.

Way of expressing ventilationWhat it actually measuresWhere it helpsWhy it misleads for an office
Outdoor air per person plus per area (ASHRAE 62.1 method)Outdoor air delivered against the people and building sources it must diluteSetting the design quantity for each zoneOnly valid if the occupancy assumed is the occupancy built
Air changes per hourTotal air moved relative to room volume, mostly recirculatedRooms where the requirement relates to the room itselfDoes not say how much of the air is outdoor air, or scale with people
Indoor CO2 readingHow well exhaled air is being diluted, in practiceChecking performance, controlling ventilation by occupancyIgnores pollutants that do not come from people
Cooling capacityHow much heat the plant can removeSizing the cooling plantSays nothing about ventilation at all

CO2 is an indicator, not a pollutant limit

People exhale carbon dioxide. In a space where people are the main source, the gap between indoor and outdoor CO2 widens when outdoor air per person falls. That makes CO2 a practical, cheap proxy for one question: is the outdoor air the design intended actually reaching the people in this room?

It is not a measure of overall air quality. ASHRAE 62.1 sets ventilation as outdoor airflow, not as an indoor CO2 concentration, and a low CO2 reading proves nothing about emissions from new finishes, cleaning products, particulates or polluted outdoor air drawn into the intake. Single-number CO2 thresholds that circulate online are rules of thumb, not requirements of the standard.

Used properly, CO2 monitoring is valuable:

  • Compare indoor readings with the outdoor level, which varies by location and time of day, rather than reading an indoor figure in isolation.
  • Watch the trend through a day. A room whose CO2 climbs steadily as it fills is telling you outdoor air per person is short.
  • Place sensors in the breathing zone, away from supply terminals, doors and people's faces, and keep them calibrated.
  • In meeting rooms and other variable-occupancy spaces, CO2 can drive demand-controlled ventilation, varying outdoor air with occupancy. ASHRAE 62.1 sets conditions on its use, and the design engineer decides where it fits.

Sensors are most useful when connected to the controls rather than displayed on a wall; building management systems are where that trend data is logged and acted on.

Why ACH is the wrong way to specify an office

Specifications still arrive asking for "so many air changes per hour" for an office. The figure can be met while the occupants still lack outdoor air, because air changes count total air movement against room volume, and in an office that air is mostly recirculated. It also does not move when headcount does, and it changes with ceiling height for the same airflow. Air changes per hour explains where ACH is the right metric. For an office, specify the outdoor air basis and the occupancy it is designed for.

Fresh air in landlord-supplied systems

In many multi-tenant buildings, outdoor air is treated centrally and delivered through a riser at a fixed quantity per floor, sized on the landlord's assumed occupancy. The tenant's fit-out distributes it. That arrangement works until the tenant's seating plan is denser than the landlord assumed, at which point the floor is under-ventilated by design, not by fault.

Questions to settle in design, in writing, with the landlord:

  • What outdoor air quantity is allocated to this floor, and on what occupancy?
  • Is it cooled, dehumidified and filtered before it arrives?
  • Does it run through all occupied hours, including late working and weekends?
  • Can the tenant add or increase outdoor air if the layout needs it, and how?

How fresh air fits into the wider plant is covered in commercial HVAC systems. Distribution, zoning and return-air problems that also cause stuffy rooms are covered in office HVAC problems after handover.

The energy trade-off

In most Indian climates outdoor air is hot, humid or both for much of the year, and treating it is a significant part of the cooling load. That creates a quiet temptation to reduce it, by undersizing, by closing dampers, or by switching fresh air off outside peak hours.

The better answer is to make the trade-off explicit. The design can size outdoor air to the real occupancy rather than a blanket figure, use demand-controlled ventilation where occupancy varies, consider recovering energy from exhaust air where the engineer finds it worthwhile, and control the system so it runs when people are present. ECBC 2017 sets energy efficiency provisions for comfort systems and controls in buildings within its scope; how those provisions apply to a project, and how they interact with the ventilation design, is for the MEP engineer to establish.

Common mistakes

  • Treating stuffiness as a temperature problem and lowering the set point.
  • Specifying an office on air changes per hour instead of outdoor air for the occupancy.
  • Densifying the floor without re-checking ventilation, because only the furniture changed.
  • Ventilating meeting rooms at open-plan density, then wondering why they feel airless within an hour.
  • Reading CO2 as a full air quality score, or reading it without the outdoor comparison.
  • Closing fresh air dampers to save energy without anyone recording the decision or its effect.
  • Assuming the landlord's fresh air suits your headcount without asking what it was sized for.

What to ask your designer

  • Which edition of ASHRAE 62.1, or which other basis, does the ventilation design use, and what occupancy does each zone assume?
  • How do meeting rooms and training rooms get their outdoor air?
  • Where does outdoor air come from, and is it treated and filtered before supply?
  • Will CO2 be monitored, where, and will it control anything?
  • How will outdoor air quantities be measured and recorded at commissioning?
  • What happens to ventilation if we add desks later?

Standards referenced

Ventilation and acceptable indoor air quality, including the ventilation rate procedure, in ASHRAE 62.1; air conditioning, heating and mechanical ventilation provisions in NBC 2016, Part 8; energy efficiency of comfort systems and controls in ECBC 2017. Ventilation rates, the governing standard edition, occupancy assumptions and control strategy for a specific building must be established by the project's MEP engineer and consultants; nothing on this page replaces that design.

Standards referenced

  • ASHRAE 62.1 — Ventilation and acceptable indoor air quality - ventilation rate procedure (ASHRAE)
  • NBC 2016, Part 8 — Building services - air conditioning, heating and mechanical ventilation (Bureau of Indian Standards)
  • ECBC 2017 — Comfort systems and controls (Bureau of Energy Efficiency)

Frequently asked

Because cooling and ventilation are different jobs. Most office air conditioning recirculates the same air and cools it; the outdoor air that replaces what people have breathed is a separate, smaller quantity. If that quantity is undersized for the headcount, not reaching the floor or turned down to save energy, the room stays cool and still feels stale.

ASHRAE 62.1 sets ventilation as outdoor airflow, not as an indoor CO2 limit, so there is no single figure in it to design to. Numbers quoted online are rules of thumb. A CO2 reading is most useful compared with the outdoor level and tracked over a day: if it climbs steadily as a room fills, outdoor air per person is falling short. The design engineer should interpret it.

No. CO2 tracks how well the air people exhale is being diluted. It says nothing about emissions from finishes and furniture, cleaning products, particulates or outdoor pollution drawn in through the intake. That is one reason ASHRAE 62.1 includes an area-based component in addition to the per-person one, and why filtration is a separate design question.

Sometimes, but outdoor air in most Indian climates has to be cooled and dehumidified before it is supplied, so more of it means more cooling load and energy. The right fix may be rebalancing distribution, adding demand-controlled ventilation to meeting rooms, or increasing the supply to match the real occupancy. The MEP engineer should diagnose before anything is changed.

It depends on the building and the lease. In many multi-tenant buildings outdoor air comes from a central treated fresh air system at a fixed quantity per floor, and the tenant distributes it. The handover schedule should state the quantity allocated, the occupancy it assumed and who operates the system. If your headcount is higher, the gap has to be resolved with the landlord in design.

It varies the outdoor air supplied to a zone according to how many people are in it, often using a CO2 sensor as the occupancy signal. It suits spaces whose occupancy swings widely, such as meeting and training rooms. ASHRAE 62.1 sets conditions on its use, so whether and how it is applied in a project is for the design engineer to decide.

Related