Warm Edge Spacer Bar in Insulated Glass Units
By Dhruv Agarwal · · 1 min read
What it is
The perimeter bar that separates the two panes of an insulated glass unit, holds the desiccant that keeps the cavity dry, and carries the seals that keep moisture out.
It is the component that decides how long a double-glazed unit lasts.
Specification at a glance
| Property | Typical specification |
|---|---|
| Material | Stainless, thermoplastic, or composite |
| Conductivity | Low; "warm edge" class stated |
| Desiccant | Molecular sieve within the spacer |
| Primary seal | Polyisobutylene, the vapour barrier |
| Secondary seal | Silicone or polysulphide, the structural bond |
| Testing | EN 1279 or ASTM E2190 |
The two seals do different jobs
This is the detail that matters and is routinely misunderstood:
- The primary seal (PIB) is the moisture barrier. It stops water vapour entering the cavity.
- The secondary seal holds the two panes together structurally and protects the primary seal.
For structurally glazed facades the secondary seal must be silicone, because polysulphide is not UV stable and structural glazing exposes the edge seal to sunlight. Using a polysulphide unit in a structurally glazed facade is a known, repeated and expensive failure.
Where projects go wrong
- Aluminium spacers in air-conditioned buildings, then condensation complaints that get blamed on the AC.
- Polysulphide secondary seal in a structurally glazed or exposed-edge application.
- Undrained glazing rebate. Standing water attacks the secondary seal and the unit fogs in a few years.
- Spacer unspecified, so the cheapest option is supplied silently.
- Units stored flat or in sun on site before installation, stressing the seal before the building is even complete.
Standards referenced
Insulating glass unit durability testing under EN 1279 and ASTM E2190. Fenestration U-value targets under ECBC 2017.
Standards referenced
- EN 1279 — Insulating glass units — long-term test methods
- ECBC 2017 — Building envelope — fenestration U-value
- ASTM E2190 — Insulating glass unit performance and evaluation