Cat6 Cable Calculator: Boxes of Cable for an Office Fit-Out

Cat6 horizontal cable is bought in boxes, usually of 305 m, and every run from the rack to an outlet must be one continuous length. The order therefore follows from how many whole runs fit in a box: runs per box = box length ÷ run length, rounded down, and boxes = data points ÷ runs per box, rounded up.

By Dhruv Agarwal · · 4 min read

Cat6 cable calculator

nos
points
nos
nos
nos
nos
points

Printers, display screens, access control, spare outlets.

m

Along the tray or trunking route, not a straight line.

m

Checked against the 90 m limit. 0 to skip.

Assumptions (edit to match your project)
points
points
points

Some designs pull two cables to each access point.

m
m
%

Bends, drops from the tray and dressing in the rack.

m

305 m (1,000 ft) is the usual box.

Boxes to order

30

5 whole runs from each 305 m box

Data points

150

One cable run each

Cable length

8,003 m

53.35 m a run, including slack and wastage

Simple length ÷ box

27

26.24 boxes; ignores that a run cannot be joined

Points and cable
Workstations 60 × 2120
Cabins 4 × 28
Meeting rooms 3 × 26
Access points 6 × 16
IP cameras8
Other points2
Total points150
Cable left in box ends1,148 m
Boxes to order30

How this was calculated

  • Run = (45 + 3 + 0.5) × 1.1 = 53.35 m
  • Runs per box = floor(305 / 53.35) = 5
  • Boxes = ceil(150 / 5) = 30
  • Compare: 150 × 53.35 = 8,002.5 m; / 305 = 26.24 → 27 boxes
  • Installed run = 45 + 3.5 = 48.5 m average, 83.5 m longest (limit 90 m)

Send this result on WhatsApp

Your figures go with the message, so our team can reply on them directly.

Send on WhatsApp

Get a detailed quote

Indicative figures for early planning, based only on the inputs and assumptions above. This is not a design, a quotation or a compliance check. A qualified engineer or consultant must confirm any figure before it is used to order, build or sign.

What it calculates

For the horizontal data cabling in a fit-out, the calculator gives:

  • the total data points, from workstations, cabins, meeting rooms, access points, cameras and other outlets;
  • the cable per run, with slack and wastage;
  • the number of whole runs from one box;
  • the boxes to order, compared with the simple total length ÷ box length;
  • a warning when an installed run exceeds the 90 m permanent link in ANSI/TIA-568.

Inputs

Workstations and data points per workstation give most of the points. Cabins, meeting rooms, wireless access points, IP cameras and other points add the rest; enter 0 for any that do not apply.

Average route length is the distance from the rack to an outlet along the cable tray or trunking route, not a straight line.

Longest route is optional and is only used for the 90 m check.

The assumptions panel holds the points per cabin, meeting room and access point, the slack at the rack and outlet ends, the wastage on each run and the box length.

Method

  1. Points = workstations × points each + cabins × points each + meeting rooms × points each
    • access points × points each + cameras + other points.
  2. Run = (average route + rack slack + outlet slack) × (1 + wastage).
  3. Runs per box = box length ÷ run, rounded down.
  4. Boxes = points ÷ runs per box, rounded up.
  5. For comparison: total cable = points × run, and total ÷ box length, rounded up.
  6. Installed run = route + rack slack + outlet slack, checked against 90 m.

ANSI/TIA-568 limits the permanent link of horizontal cabling to 90 m. Wastage is treated as an ordering allowance and is not counted in the installed run.

Assumptions

AssumptionDefaultNotes
Points per cabin2Set by the IT brief
Points per meeting room2Add for screens and conferencing equipment
Points per access point1Some designs pull two
Service loop at the rack3 mFollow the cabling specification
Slack at the outlet0.5 mFollow the cabling specification
Wastage on each run10%Bends, drops from the tray, dressing in the rack
Cable in one box305 mThe usual box (1,000 ft); replace with your product's data sheet

Limitations

  • Every run is taken at the average length. In practice short and long runs can be pulled from the same box, so the true number of boxes usually falls between the box-based and simple figures.
  • The 90 m check uses the routes you enter. It does not know the layout; a run that is longer than the longest route entered will not be flagged.
  • Backbone cabling between racks or floors, fibre, and cabling for systems such as access control or audio-visual equipment that use other cable types are not counted.
  • Patch cords, panels, jacks, faceplates, racks and containment are separate items.
  • Cable type and performance (category, shielding, sheath rating for the route) come from the network design, not from this calculation.

Worked example

An office with 60 workstations at 2 points each, 4 cabins and 3 meeting rooms at 2 points each, 6 access points, 8 IP cameras and 2 other points, a 45 m average route, an 80 m longest route, 3 m and 0.5 m of slack, 10% wastage and 305 m boxes:

StepCalculationResult
Points120 + 8 + 6 + 6 + 8 + 2150
Run(45 + 3 + 0.5) × 1.1053.35 m
Runs per box305 ÷ 53.35 = 5.72, rounded down5
Boxes150 ÷ 530
Simple comparison150 × 53.35 = 8,002.5 m; ÷ 305 = 26.24, rounded up27
Installed runs45 + 3.5; 80 + 3.548.5 m and 83.5 m, under 90 m

The office needs 30 boxes of 305 m, not the 27 that total length alone suggests, and about 1,148 m is left in box ends. No warning is shown, as the longest installed run is 83.5 m. At a 60 m average route the run becomes 69.85 m, only 4 fit in a box, and the order rises to 38 boxes.

How engineers use it

On a fit-out, the IT brief and furniture layout set the data points, and the cabling designer places racks so every outlet is within the permanent link limit. The installer then prepares a cable schedule with the route length of each run, groups runs by box so long and short pulls share a box, and orders from that schedule. Containment is sized for the cable count and future growth.

When a professional design must replace it

Use the calculator for an early estimate or to check a cabling quotation. Replace it with a cabling design and cable schedule before ordering, and wherever the layout has more than one rack location, long routes near the 90 m limit, cabling through a raised floor or ceiling void with its own requirements, or a network that must be tested and documented to a specific standard. The network designer decides the cable category, rack positions and test requirements.

Standards referenced

  • TIA-568 — Commercial building telecommunications cabling — 90 m maximum horizontal cable (permanent link) (Telecommunications Industry Association)

Frequently asked

Work out the cable for one run: route length plus slack at both ends, plus a wastage allowance. Divide the box length by that, rounding down, for the whole runs one box gives, then divide the number of points by it and round up. 150 points at a 45 m average route, with 3.5 m of slack and 10% wastage, give 53.35 m runs, 5 runs a 305 m box and 30 boxes.

Because a horizontal run cannot be joined part way, so the length left in a box after the last whole run is usually wasted. In the default example the total is about 8,003 m, which divided by 305 m suggests 27 boxes, but only 5 runs fit in each box, so 30 are needed. The real figure sits between the two when long and short runs are pulled from the same box.

ANSI/TIA-568 limits the permanent link, the fixed horizontal cable from the patch panel in the rack to the outlet, to 90 m. Patch cords at each end are extra. The calculator warns when an average or longest route plus slack goes over 90 m; the usual answer is a rack closer to the outlets, which the network designer decides.

A service loop at the rack lets the cable be re-terminated or moved within the rack, and a little slack at the outlet allows re-termination there. The defaults are 3 m at the rack and 0.5 m at the outlet; follow the cabling designer's or installer's specification for the project.

Yes. The method is the same for any horizontal cable sold in boxes or reels: enter the box or reel length from the data sheet. Cat6A cable is thicker, which affects containment fill and bend radius, but not the run count.

No. It counts horizontal cable only. Patch panels, jacks, faceplates, patch cords, racks and containment are separate items, usually counted from the same list of data points.

Related

More in Calculators

All Calculators →

Planning an office or commercial project?

Tell us what you are planning. Message our team on WhatsApp, call us, or leave your number and we will call you back.

Request a callback