Phenolic Foam Insulation — Thin Build-Up, Low Lambda
By Dhruv Agarwal · · 1 min read
What it is
A rigid closed-cell phenolic resin foam, usually faced with aluminium foil or a glass tissue. It has the lowest thermal conductivity of the common rigid insulation boards.
Specification at a glance
| Property | Typical specification |
|---|---|
| Standard | EN 13166 |
| Thermal conductivity | Approximately 0.018 — 0.021 W/mK |
| Thickness | 20mm — 100mm |
| Facing | Aluminium foil, or glass tissue |
| Fire class | Named EN 13501-1 class; chars rather than melts |
| Friability | Higher than PIR; handle with care |
Thickness for a U-value, compared
Indicative, before thermal bridging, for approximately 0.25 W/m²K:
| Material | Approximate thickness |
|---|---|
| Phenolic | ~80mm |
| PIR | ~90mm |
| EPS | ~150mm |
| Rock wool | ~150mm |
That difference is the entire argument for phenolic. Where it does not matter, it usually is not worth the premium.
Where it belongs
Refurbishments with fixed floor-to-ceiling heights · duct insulation in congested ceiling voids · roof build-ups where upstand heights are already set by existing thresholds · any envelope where the U-value target cannot be met in the available depth with a cheaper board.
Where projects go wrong
- Used where depth is not constrained, paying a premium for nothing.
- Handled roughly. Crumbled edges leave gaps in the insulation line.
- Assumed non-combustible. It is not.
- Facing damaged and not repaired, losing the vapour control function.
- Cut undersize, leaving gaps that undo the thermal advantage the material was chosen for.
Standards referenced
Phenolic foam products under EN 13166. Reaction-to-fire classification to EN 13501-1. Opaque assembly U-value targets under ECBC 2017.
Standards referenced
- EN 13166 — Thermal insulation products — factory made phenolic foam
- EN 13501-1 — Reaction to fire classification
- ECBC 2017 — Building envelope — opaque assembly U-value