# Pre-Insulated Duct — PIR Panel Ductwork

> Pre-insulated duct is ductwork made from rigid PIR panel faced with aluminium on both sides, cut and folded into sections on site so the insulation and the duct are one component. It needs less void height and is much lighter than GI ductwork, but it is less robust, pressure-limited, and its PIR core is combustible.

## What it is

Ductwork made from **rigid PIR panel faced with aluminium on both sides**, cut
and folded into sections on site. The insulation and the duct are the same
component.

## Specification at a glance

| Property | Typical specification |
| --- | --- |
| Panel | PIR core, aluminium facings both sides |
| Panel thickness | 20mm — 30mm typical |
| Facing | Aluminium foil, thickness stated |
| Standard | EN 13403 for non-metallic ducts |
| Fire class | Named EN 13501-1 classification |
| Pressure limit | Stated by manufacturer; not unlimited |

## Against GI ductwork

| | Pre-insulated PIR | GI with wrap |
| --- | --- | --- |
| Void height needed | Less | More |
| Weight | Much lighter | Heavy |
| Install sequence | One operation | Fabricate, fit, then insulate |
| Robustness | Lower; damages easily | High |
| Pressure capability | Limited | Wide range |
| Outdoor use | Needs weather jacket | Standard |

## Where it earns its place

Tight ceiling voids in fit-outs where the slab-to-slab height is fixed and
services must be stacked · refurbishments where structural hanger capacity is
limited · fast-track programmes where removing the separate insulation trade
saves real days · low and medium pressure comfort cooling in office space.

## Where projects go wrong

- **Used in the wrong location** — kitchen extract, exposed plant rooms, or
  outdoors without a jacket.
- **Fire class not checked** against the route the duct takes.
- **Joints poorly made.** The system relies on correct corner profiles and
  taping; a rushed joint leaks and the aluminium facing tears.
- **Hangers over-tightened**, crushing the panel and reducing the free area.
- **Pressure class exceeded**, causing panel deflection and joint failure.

## Standards referenced

Non-metallic duct requirements under **EN 13403**. Reaction-to-fire
classification to **EN 13501-1**. Duct insulation requirements under
**ECBC 2017**.

## Frequently asked questions

### What does pre-insulated duct actually save?

Height, weight and time. The insulation is the duct wall rather than a wrap applied afterwards, so the overall section is smaller for the same free area — which matters when the ceiling void is tight and services are stacked. It is a fraction of the weight of GI, so hanger loads drop, and it is one trade and one operation instead of fabricate, install, then insulate.

### Is it acceptable on fire safety grounds?

It depends on the product and where it runs. The panels are aluminium faced with a PIR core, so the core is combustible even though the facings are not. Products have a named EN 13501-1 classification and that class must be checked against the application, particularly in escape routes, shafts and high-occupancy spaces. It is not a substitute for a fire-rated duct where one is required.

### Where should it not be used?

Outdoors without a designed weather jacket, in kitchen extract carrying grease, in high-pressure systems beyond the manufacturer's stated limit, and anywhere the duct is exposed to impact. The panel is far less robust than GI, so plant rooms, car parks and service corridors where ladders and trolleys pass are better served by sheet metal.

## Sources

- [EN 13403](https://standards.cencenelec.eu/ords/f?p=CEN:105) — Ventilation for buildings — non-metallic ducts
- [EN 13501-1](https://standards.cencenelec.eu/ords/f?p=CEN:105) — Reaction to fire classification
- [ECBC 2017](https://beeindia.gov.in/) — HVAC — duct insulation

---